TGR 39

Residential Series – Produk andalan dengan suara halus dan compact design, mesin YANMAR produksi jepang dengan STAMFORD Generator Standard UK. Sangat cocok untuk ruangan kecil dan mengurangi polusi suara di perumahan atau perkantoran.


Minat dengan produk ini ?


*Standard delivery term Ex Work warehouse

YANMAR® Heavy-Duty Engine
Rugged industrial diesel delivers reliable power, low emissions and fast response to load changes.

STAMFORD® Brushless Alternator
Low reactance 2/3 pitch windings; low waveform distortion with non-linear loads, fault clearing short-circuits capability, and class H insulation.

Control System
DeepSea electronic control is the industry leading standard equipment and provides total genset system integration, including automatic remote starting/stopping, precise voltage regulation, alarm and status message display.

Cooling System
Standard integral set-mounted radiator system, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat.

Enclosures
Optional weather-protective and sound-attenuated enclosures are available.

Warranty
Using all genuine parts and covered by comprehensive 1 year warranty, applicable to nation-wide dealership network.

SPECIFICATION

AC Generator ModelTGR 391 Phase3 Phase
Output Rating (kVA)50 Hz380VPrime27.932.0
Standby30.234.3
60 Hz440VPrime30.539.2
Standby30.541.9
Rated Current (A)50 Hz380VPrime40.346.2
Standby43.649.6
60 Hz440VPrime44.151.5
Standby44.155.0
Stamford Alternator Model50 HzS1L2R1S1L2J1
60 HzUCI224C1S1L2J1
Yanmar Engine Model4TNV98
Fuel Consumption 100% LoadL/Hr50 Hz8.85
60 Hz10.49
Sound Level dBA from 1 m / 7mdBA65

 

Dimension 35-40 kva

*Approx dimension, Trupower reserves the right to make change in model and technical specifications.
*Dimension in millimeters

STANDARD

Genset          : ISO 8528.
Engine          : ISO 2046, DIN 6271.
Alternator    : VDE 0530, NEMA MGI-32, IEC34, AS1359.

RATING DEFINITION

Emergency Standby Power (ESP)
Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.

Limited-Time Running Power (LTP)
Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528.

Prime Power (PRP)
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.

Base Load (Continuous) Power (COP)
Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.

PUNYA PERTANYAAN? HUBUNGI SALES HOTLINE KAMI

Pelajari lebih lanjut tentang produk Generator Set kami

+62 812 1312 3544

Related Product

Sedang mencari produk lain? Klik disini untuk kembali ke produk generator set lainnya